LayerZero Power Systems
Contact Us
LayerZero Power Systems, Inc.

LayerZero News

LayerZero Completes 150A-600A OPTS Fault Testing At KEMA-Powertest Labs

 

Chagrin Falls, Ohio (April 27, 2002) LayerZero Power Systems, Inc. is pleased to announce the successful completion of Closing and Withstand tests of its 150A-600A Optical Power Transfer Switch (OPTS) product line at KEMA-Powertest Labs in Chalfont, PA. As a result of the testing LayerZero OPTS withstand ratings are as follows:

 

STS Current Rating (Two-source and Three-source systems)

Withstand rating for 480V, Three-wire + Ground systems

Withstand Rating for 208V, Four-wire + Ground systems

150A

65kA

100kA

250A

65kA

100kA

400A

100kA

150kA

600A

100kA

150kA

 

Based on test results, LayerZero’s 150-600A product family meets the criteria of High Energy (Type III) Static Transfer Switches. Upon application of faults with the rated available fault current, the solid state switches (SCRs) neither ruptured nor shorted.

 

In practical terms this enhanced survivability of the power stage under fault conditions would allow a mission-critical site to instantly recover from a downstream catastrophic fault/failures without having to perform any immediate repair to the LayerZero OPTS.

 

For more information about LayerZero Power Systems, visit http://www.layerzero.com

 

Previous