ePODs 400-500 kVa 480 V 120/208 V Up to (12) SafePanel Subfeeds, 800A or Smaller PDU
Power Distribution Unit

Product Overview

The LayerZero ePODs: 400-500 kVa 480 V 120/208 V Subfeeds PDU is a web-enabled power distribution unit (PDU) with a transformer, safepanel distribution, and subfeed distribution. It is a SIMO configuration (single input, multiple outputs), meaning that it has a single input power source and multiple output circuits. The ePODs PDU is ideal for application that require high-reliability power distribution.

The core functionality of the LayerZero ePODs PDU is to distribute power to a large number of circuits. It can accommodate transformers with up to 400-500 kVA capacity and has a subfeed transformer distribution system. This makes it ideal for applications with high power requirements, such as data centers and large industrial facilities.

The ePODs: 400-500 kVa 480 V 120/208 V Subfeeds PDU also features a number of safety features, including safepanel distribution, dead front doors, no exposed live parts (NELP) and polycarbonate windows. These features help to protect users and equipment from electrical hazards.

The LayerZero ePODs Subfeeds PDU is a versatile and reliable power distribution solution that is ideal for a wide range of applications, making it a safe and reliable way to distribute power to critical applications.

Documents and Downloads

A one line diagram is a symbolic representation of three-phase electric power systems, depicting the paths for power flow between entities of the power distribution system.

Download
One Line

Guideform specifications include the requirements, specifications, and considerations of installing LayerZero equipment.

Download
Guideform Specification

Product brochures contain information about the product's features, benefits, and specifications.

Download
Product Brochure

Product Specifications

Product Specifications

Physical Specifications

WeightPlease contact LayerZero engineering
DimensionsPlease contact LayerZero engineering
ClearancesPlease contact LayerZero engineering
Heat DissipationPlease contact LayerZero engineering
ColorLight Gray, Black
WarrantyOne-Year Limited Warranty
CSA RatingCertified to CSA STD C22.2#60950-1
UL RatingConforms to UL STD 60950-1
INSIGHT IR CamerasOptional (INSIGHT IR Portholes are standard)
Extended WarrantyOptional (Please contact LayerZero Sales)

ePODs Configuration

System Input Voltage480V, 3-Phase, 3-Wire + Ground
System Output Voltage240/415V, 3-phase, 4-wire + Ground
System Output Voltage - 1st AlternateNo
System Output Voltage - 2nd AlternateNo
Transformer Size500kVA
Secondary Neutral Rating200%
eSTS IntegrationNo
Input Feeder TerminationsTwo-hole Compression Lug Terminals
Presence of Primary Side DistributionNo
Transformer Input Current Rating601A
Transformer Output Current Rating696A
Presence of Secondary Side DistributionYes
Secondary Distribution SideFront
Secondary Distribution OrientationFront-facing
Distribution TypeSubfeed Distribution
Secondary Subfeed Type1200A SafePanel
Secondary Subfeed Panel Board Quantity1
Presence of Primary Main Circuit BreakerYes
Presence of Primary Auxiliary Circuit BreakerNo
Sync Check Relay RequiredN/A
Presence of Kirk Key InterlockN/A

Primary Main Circuit Breaker (CB601)

Frame Rating800
Circuit Breaker TypeElectronic Trip (LSI)
Circuit Breaker Mounting TypeFixed
Max Steady State Rating800
Percent Rating80
Fault Rating at Rated Voltage65kAIC @ 480VAC
Presence of Shunt Trip120VAC
Presence of CB Position IndicationsNo
Presence of Lockout/Tag-out BracketYes
Number of Poles3
SupplierABB

Transformer (T620)

Transformer size500
MaterialAluminum
k-Factork-4
Efficiency Class99+
Temperature Rise150
Inrush5X Max
Nominal Impedance6.25

PANEL 801 Subfeed Circuit Breaker 1

Frame Rating400
Circuit Breaker TypeElectronic Trip (LSI)
Circuit Breaker Mounting TypePlug-in, (2) 3/0-250 MCM load lugs
Max Steady State Rating400
Percent Rating100
Fault Rating at Rated Voltage25kAIC @ 480VAC
Presence of Shunt TripNo
Presence of CB Position IndicationsYes - monitored internally
Presence of Lockout/Tag-out BracketYes
Number of Poles3
SupplierABB

PANEL 801 Subfeed Circuit Breaker 2

Frame Rating400
Circuit Breaker TypeElectronic Trip (LSI)
Circuit Breaker Mounting TypePlug-in, (2) 3/0-250 MCM load lugs
Max Steady State Rating400
Percent Rating100
Fault Rating at Rated Voltage25kAIC @ 480VAC
Presence of Shunt TripNo
Presence of CB Position IndicationsYes - monitored internally
Presence of Lockout/Tag-out BracketYes
Number of Poles3
SupplierABB

PANEL 801 Subfeed Circuit Breaker 3

Frame Rating400
Circuit Breaker TypeElectronic Trip (LSI)
Circuit Breaker Mounting TypePlug-in, (2) 3/0-250 MCM load lugs
Max Steady State Rating400
Percent Rating100
Fault Rating at Rated Voltage25kAIC @ 480VAC
Presence of Shunt TripNo
Presence of CB Position IndicationsYes - monitored internally
Presence of Lockout/Tag-out BracketYes
Number of Poles3
SupplierABB

PANEL 801 Subfeed Circuit Breaker 4

Frame Rating400
Circuit Breaker TypeElectronic Trip (LSI)
Circuit Breaker Mounting TypePlug-in, (2) 3/0-250 MCM load lugs
Max Steady State Rating400
Percent Rating100
Fault Rating at Rated Voltage25kAIC @ 480VAC
Presence of Shunt TripNo
Presence of CB Position IndicationsYes - monitored internally
Presence of Lockout/Tag-out BracketYes
Number of Poles3
SupplierABB

SafePanel 1 (PANEL 801)

Current1200
Withstand65
SupplierABB

Secondary Side SPD (SPD620)

Voltage240/415
Number of Wires4
TypeType 2 SPD
Surge Withstand40
Presence of Alarm IndicationYes - monitored internally

Safety Features

Safety Features

The LayerZero ePODs is designed for maximum operator safety. It uses a sectionalized design, which means that the power quality monitoring and distribution are housed in a separate section from the circuit breakers and customer cable connections. This compartmentalized design allows the equipment to be safely operated and serviced.

In normal operation, the inner dead-front doors of the ePODs remain closed..

A polycarbonate window in the door allows operators to safely view the status LEDs in the control section without opening the door. INSIGHT IR® cameras (optional) or IR Ports (standard) provide the ability to monitor the temperatures of critical connections with the doors safely closed.

The LayerZero Power Systems ePODs is a safe and reliable piece of equipment that is designed to protect operators and equipment.

Reliability Features

Reliability Features

The LayerZero ePODs Power Distribution Unit is designed to provide reliable power distribution for critical applications. It offers robust features and advanced technology to ensure consistent and efficient power delivery.

The ePODs PDU is built with high-quality components. It features silver-plated connections, which enhance conductivity and minimize resistance, ensuring optimal power transmission. The use of machined hardware further enhances reliability of the unit by ensuring that when connections are torqued, they stay that way.

In addition, the ePODs PDU is designed with a seismic rating, making it suitable for installations in seismically active areas. This ensures the stability and performance of the unit, even during earthquake events.

Furthermore, the ePODs PDU incorporates serialized board tracking in a dynamic and active database, allowing for easy identification and tracking of individual boards within the unit. This feature simplifies maintenance and troubleshooting, facilitating efficient management of the power distribution unit.

Power Quality Monitoring Features

Power Quality Monitoring Features

The LayerZero ePODs is equipped with an advanced Power Quality Monitoring (PQM) system that provides local and remote access using non-proprietary protocols. The PQM system includes basic monitoring, alarms, waveform capture, and ITIC plotting capabilities.

The ITIC plotting utility is used to audit the quality of transfers. Systems can be configured to automatically email users waveform captures as an attachment. This ensures that users are notified of events as they happen, without having to manually check for waveform captures.

Connectivity Features

Connectivity Features
  • Ethernet Connectivity: This protocol is used to connect the switch to a network.
  • Modbus/TCP: This protocol is used to communicate with BMS systems.
  • SNMP Connectivity: This protocol is used to manage the switch remotely.