Product Overview

The LayerZero eRDP-FS (eRDP-1) is a web-enabled remote distribution panel (eRDP) with subfeed distribution. It is a MIMO configuration (multiple inputs, multiple outputs), meaning that it can have multiple input power sources and multiple output circuits. The eRDP is ideal for applications that require high-reliability power distribution in a space-saving design.

The core functionality of the LayerZero eRDP is to distribute power to a large number of circuits. It can accommodate subfeed circuit breakers, including both finger-safe and non-finger-safe breakers. This makes it ideal for applications with high power requirements, such as data centers and large industrial facilities.

The eRDP also features a number of safety features, including SafePanel® distribution, dead front doors, no exposed live parts (NELP) and polycarbonate windows. These features help to protect users and equipment from electrical hazards.

If you are looking for a high-reliability, safe, and versatile power distribution solution, the LayerZero eRDP is a great option.

Documents and Downloads

A one line diagram is a symbolic representation of three-phase electric power systems, depicting the paths for power flow between entities of the power distribution system.

Download
One Line

A product outline is a technical engineering drawing showing mechanical characteristics of our products.

Download
Product Outline

Product Specifications

Product Specifications

Physical Specifications

Dimensions88" x 36" x 36" (2240 mm x 905 mm x 905 mm)
Weight674 lbs (306 kg)
ClearancesFront 36” [915mm] Rear 0 Left 1” [25mm] Right 1” [25mm] Top 18” [457mm]
ColorGray, Black
WarrantyOne-Year Limited Warranty
CSA RatingCertified to CSA STD C22.2#29
UL RatingConforms to UL STD 67
Distribution TypeSubfeed Distribution

System Specifications

System Input Voltage600V, 3-Phase, 3-Wire + Ground
System Output Voltage120/208V, 3-phase, 4-wire + Ground
System Output Voltage - 1st AlternateNo
System Output Voltage - 2nd AlternateNo
Transformer Size150kVA
Secondary Neutral Rating200%
eSTS IntegrationNo
Input Feeder TerminationsTwo-hole Compression Lug Terminals
Presence of Primary Side DistributionNo
Transformer Input Current Rating144A
Transformer Output Current Rating416A
Presence of Secondary Side DistributionYes
Secondary Distribution SideBoth
Secondary Distribution OrientationSide-facing
Distribution Type42-pole Branch Circuit Distribution and Subfeed Breakers
Total Quantity of Branch Circuit Panel Boards4
Total Quantity of 225A Branch Circuit SafePanels®4
Total Quantity of 400A Branch Circuit SafePanels®0
Exposed Live Parts or No Exposed Live PartsExposed Live Parts (ELP)
Subfeed Circuit Breaker TypeSubfeed Distribution
Secondary Subfeed Type1200A SafePanel®
Secondary Subfeed Panel Board Quantity1
Presence of Primary Main Circuit BreakerYes
Presence of Primary Auxiliary Circuit BreakerNo
Sync Check Relay RequiredN/A
Presence of Kirk Key InterlockN/A

Primary Main Circuit Breaker (CB601)

Frame Rating250
Circuit Breaker TypeElectronic Trip (LSIG)
Circuit Breaker Mounting TypeFixed
Max Steady State Rating250
Percent Rating80
Fault Rating at Rated Voltage65kAIC @ 600VAC
Presence of Shunt Trip24VDC
Presence of CB Position IndicationsYes - wired to terminal blocks
Presence of Lockout/Tag-out BracketYes
Number of Poles3
SupplierABB

Transformer (T620)

Transformer size150
MaterialCopper
k-Factork-20
Efficiency ClassPer DOE 2016
Temperature Rise150
Inrush5X Max
Nominal Impedance5.5

Secondary Main Circuit Breaker (CB701)

Frame Rating600
Circuit Breaker TypeElectronic Trip (LSI)
Circuit Breaker Mounting TypeFixed
Max Steady State Rating600
Percent Rating80
Fault Rating at Rated Voltage65kAIC @ 240VAC
Presence of Shunt TripNo
Presence of CB Position IndicationsYes - monitored internally
Presence of Lockout/Tag-out BracketYes
Number of Poles3
SupplierABB

Branch Circuit Panel Board 1 Main Circuit Breaker (CB821)

Frame Rating250
Circuit Breaker TypeElectronic Trip (LS/I)
Circuit Breaker Mounting TypePlug-in to SafePanel®
Max Steady State Rating250
Percent Rating80
Fault Rating at Rated Voltage65kAIC @ 240VAC
Presence of Shunt TripNo
Presence of CB Position IndicationsYes - monitored internally
Presence of Lockout/Tag-out BracketYes
Number of Poles3
SupplierABB

Branch Circuit Panel Board 1 (PANEL 821)

Rating - Phases225
Rating - Neutral225
Rating - Ground225
Withstand22
SupplierSchneider/Square D

Branch Circuit Panel Board 2 Main Circuit Breaker (CB822)

Frame Rating250
Circuit Breaker TypeElectronic Trip (LS/I)
Circuit Breaker Mounting TypePlug-in to SafePanel®
Max Steady State Rating250
Percent Rating80
Fault Rating at Rated Voltage65kAIC @ 240VAC
Presence of Shunt TripNo
Presence of CB Position IndicationsYes - monitored internally
Presence of Lockout/Tag-out BracketYes
Number of Poles3
SupplierABB

Branch Circuit Panel Board 2 (PANEL 822)

Rating - Phases225
Rating - Neutral225
Rating - Ground225
Withstand22
SupplierSchneider/Square D

Branch Circuit Panel Board 3 Main Circuit Breaker (CB823)

Frame Rating250
Circuit Breaker TypeElectronic Trip (LS/I)
Circuit Breaker Mounting TypePlug-in to SafePanel®
Max Steady State Rating250
Percent Rating80
Fault Rating at Rated Voltage65kAIC @ 240VAC
Presence of Shunt TripNo
Presence of CB Position IndicationsYes - monitored internally
Presence of Lockout/Tag-out BracketYes
Number of Poles3
SupplierABB

Branch Circuit Panel Board 3 (PANEL 823)

Rating - Phases225
Rating - Neutral225
Rating - Ground225
Withstand22
SupplierSchneider/Square D

Branch Circuit Panel Board 4 Main Circuit Breaker (CB824)

Frame Rating250
Circuit Breaker TypeElectronic Trip (LS/I)
Circuit Breaker Mounting TypePlug-in to SafePanel®
Max Steady State Rating250
Percent Rating80
Fault Rating at Rated Voltage65kAIC @ 240VAC
Presence of Shunt TripNo
Presence of CB Position IndicationsYes - monitored internally
Presence of Lockout/Tag-out BracketYes
Number of Poles3
SupplierABB

Branch Circuit Panel Board 4 (PANEL 824)

Rating - Phases225
Rating - Neutral225
Rating - Ground225
Withstand22
SupplierSchneider/Square D

PANEL 801 Subfeed Circuit Breaker 1

Frame Rating400
Circuit Breaker TypeElectronic Trip (LS/I)
Circuit Breaker Mounting TypePlug-in, (2) 3/0-250 MCM load lugs
Max Steady State Rating300
Percent Rating80
Fault Rating at Rated Voltage65kAIC @ 240VAC
Presence of Shunt TripNo
Presence of CB Position IndicationsYes - monitored internally
Presence of Lockout/Tag-out BracketYes
Number of Poles3
SupplierABB

SafePanel® 1 (PANEL 801)

Current1200
Withstand100
SupplierABB

Secondary Side SPD (SPD620)

Voltage120/208
Number of Wires4
TypeType 2 SPD
Surge Withstand40
Presence of Alarm IndicationYes - monitored internally

CB821 Load Side Lug

TypeMechanical Lug
Cable Size(1) 10 AWG-250MCM (Cu Only)

CB822 Load Side Lug

TypeMechanical Lug
Cable Size(1) 10 AWG-250MCM (Cu Only)

CB823 Load Side Lug

TypeMechanical Lug
Cable Size(1) 10 AWG-250MCM (Cu Only)

CB824 Load Side Lug

TypeMechanical Lug
Cable Size(1) 10 AWG-250MCM (Cu Only)

N1 Neutral Lug 821-1

TypeCompression Lug
Cable Size2/0 AWG

N1 Neutral Lug 822-1

TypeCompression Lug
Cable Size2/0 AWG

N1 Neutral Lug 823-1

TypeCompression Lug
Cable Size2/0 AWG

N1 Neutral Lug 824-1

TypeCompression Lug
Cable Size2/0 AWG

IN1G-3 Lug 822-1

TypeCompression Lug
Cable Size2 AWG

G1 Lug 823-1

TypeCompression Lug
Cable Size2 AWG

G1 Lug 824-1

TypeCompression Lug
Cable Size2 AWG

Safety Features

Safety Features

The LayerZero eRDP-FSis designed for maximum operator safety. It uses a sectionalized design, which means that the power quality monitoring is housed in a separate section from the circuit breakers and customer cable connections. This compartmentalized design allows the equipment to be safely operated and serviced.

In normal operation, the inner dead-front doors of the HD2 remain closed.

A polycarbonate window in the door allows operators to safely view the circuit breaker positions with the dead front door closed. INSIGHT IR® cameras (optional) or an IR Port (standard) provides the ability to monitor the temperatures of critical connections with the doors safely closed.

The LayerZero Power Systems eRDP-FSis a safe and reliable piece of equipment that is designed to protect operators and equipment.

Reliability Features

Reliability Features

The LayerZero eRDP-FSis a highly reliable Remote Power Panel designed to provide power distribution and monitoring for critical applications. It offers advanced safety and reliability features to ensure consistent and dependable power delivery.

The eRDP-FSis built with high-quality components, ensuring long-lasting performance and reliability. HD2 features silver-plated connections, which enhance conductivity and minimize resistance, resulting in optimal power transmission.

With its comprehensive design, the eRDP-FSis capable of meeting the demands of various operating conditions. It incorporates a seismic rating, making it suitable for installations in seismically active areas. This ensures the stability and performance of the panel, even during earthquakes.

The eRDP-FSalso incorporates serialized board tracking, enabling easy identification and tracking of individual boards within the panel. This feature simplifies maintenance and troubleshooting, such as having the ability to detect for part defects.

With its reliable performance, advanced features, and safety-focused design, the LayerZero eRDP-FSis an excellent choice for organizations that require a dependable and safe remote power panel to support their critical applications.

Power Quality Monitoring Features

Power Quality Monitoring Features

The LayerZero eRDP-FSis equipped with an advanced Power Quality Monitoring (PQM) system that provides local and remote access using non-proprietary protocols. The PQM system includes basic monitoring, alarms, waveform capture, and ITIC plotting capabilities.

The ITIC plotting utility is used to audit the quality of transfers.

Connectivity Features

Connectivity Features
  • Ethernet Connectivity: This port is used to connect to to a network.
  • Modbus/TCP: This protocol is used to communicate with BMS systems.
  • SNMP Connectivity: This protocol is used to manage the switch remotely.

Where to Buy

Find Your Sales Rep

Find My Local Representative

*Select "Allow LayerZero.com To
Know Your Location" when prompted