ePODs 400-500 480 120/208 Up to (6) Fixed Subfeeds PDU Power Distribution Unit
ePODs 400-500 480 120/208 Up to (6) Fixed Subfeeds PDU
Power Distribution Unit

Product Overview

The LayerZero ePODs: 400-500 480 120/208 Subfeeds PDU is a web-enabled power distribution unit (PDU) with a transformer, safepanel distribution, and sybfeed distribution. It is a SIMO configuration (single input, multiple outputs), meaning that it has a single input power source and multiple output circuits. The ePODs PDU is ideal for application that require high-reliability power distribution.

The core functionality of the LayeZero ePODs PDU is to distribute power to a large number of circuits. It can accommodate transformers with up to 400-500kVA capacity and has a subfeed transformer distribution system. This makes it ideal for applications with high power requirements, such as data centers and large industrial facilities.

The ePODs: 400-500 480 120/208 Subfeeds PDU also features a number of safety features, including safepanel distribution, dead front doors, no exposed live parts (NELP) and polycarbonate windows. These features help to protect users and equipment from electrical hazards.

The LayerZero ePODs Sybfeeds PDU is a versatile and reliable power distribution solution that is ideal for a wide range of applications, making it a safe and reliable way to distribute power to critical applications.

Product Specifications

Physical Specifications
Transformer Size 500kVA
Secondary Neutral Rating 200%
Color Black
eSTS Integration No
Input Feeder Terminations Two-hole Compression Lug Terminals
Presence of Secondary Side Distribution Yes
Secondary Distribution Side Front
Secondary Distribution Orientation Front-facing
Distribution Type Individually-mounted Subfeed Breakers
Total Quantity of Subfeed Circuit Breakers 6
Identical Subfeed Circuit Breakers Yes
Electrical Specifications
System Input Voltage 480V, 3-Phase, 3-Wire + Ground
System Output Voltage 120/208V, 3-phase, 4-wire + Ground
System Output Voltage - 1st Alternate ? Alternate system output voltage option, if applicable. No
System Output Voltage - 2nd Alternate ? Second alternate system output voltage option, if applicable. No
Transformer Input Current Rating 601A
Transformer Output Current Rating 1388A
Presence of Subfeed Breaker Current Monitoring No
Presence of Subfeed Breaker Power Quality Monitoring No
Presence of Primary Main Circuit Breaker Yes
Circuit Breaker Configuration ? Configuration details of the primary main circuit breaker. Primary Main Circuit Breaker (CB601)
Frame Rating ? Maximum rating of the primary main circuit breaker frame. 800
Circuit Breaker Type ? Type of circuit breaker used for the primary main circuit breaker. Electronic Trip (LS/I)
Circuit Breaker Mounting Type ? Method used for mounting the primary main circuit breaker. Fixed
Max Steady State Rating ? Maximum steady-state rating of the primary main circuit breaker. 800
Percent Rating ? Percentage of the primary main circuit breaker's maximum rating used for load calculations. 80%
Fault Rating at Rated Voltage ? Fault rating of the primary main circuit breaker at its rated voltage. 65kAIC @ 480VAC (per UL ratings)
Presence of Shunt Trip ? Indicates if the primary main circuit breaker is equipped with a shunt trip feature. 24VDC
Presence of CB Position Indications ? Indicates if the primary main circuit breaker has position indications. No
Presence of Lockout/Tag-out Bracket ? Indicates if the primary main circuit breaker has a lockout/tag-out bracket. Yes
Options
INSIGHT IR Cameras Optional (INSIGHT IR Portholes are standard)
Extended Warranty Optional (Please contact LayerZero Sales)

Documents and Downloads

A one line diagram is a symbolic representation of three-phase electric power systems, depicting the paths for power flow between entities of the power distribution system.

Download
One Line

A product outline is a technical engineering drawing showing mechanical characteristics of our products.

Download
Product Outline

Guideform specifications include the requirements, specifications, and considerations of installing LayerZero equipment.

Download
Guideform Specification

Safety Features

The LayerZero ePODs is designed for maximum operator safety. It uses a sectionalized design, which means that the power quality monitoring and distribution are housed in a separate section from the circuit breakers and customer cable connections. This compartmentalized design allows the equipment to be safely operated and serviced.

In normal operation, the inner dead-front doors of the ePODs remain closed..

A polycarbonate window in the door allows operators to safely view the status LEDs in the control section without opening the door. INSIGHT IR® cameras (optional) or IR Ports (standard) provide the ability to monitor the temperatures of critical connections with the doors safely closed.

The LayerZero Power Systems ePODs is a safe and reliable piece of equipment that is designed to protect operators and equipment.

Reliability Features

The LayerZero ePODs Power Distribution Unit is designed to provide reliable power distribution for critical applications. It offers robust features and advanced technology to ensure consistent and efficient power delivery.

The ePODs PDU is built with high-quality components. It features silver-plated connections, which enhance conductivity and minimize resistance, ensuring optimal power transmission. The use of machined hardware further enhances reliability of the unit by ensuring that when connections are torqued, they stay that way.

In addition, the ePODs PDU is designed with a seismic rating, making it suitable for installations in seismically active areas. This ensures the stability and performance of the unit, even during earthquake events.

Furthermore, the ePODs PDU incorporates serialized board tracking in a dynamic and active database, allowing for easy identification and tracking of individual boards within the unit. This feature simplifies maintenance and troubleshooting, facilitating efficient management of the power distribution unit.

Power Quality Monitoring Features

The LayerZero ePODs is equipped with an advanced Power Quality Monitoring (PQM) system that provides local and remote access using non-proprietary protocols. The PQM system includes basic monitoring, alarms, waveform capture, and ITIC plotting capabilities.

The ITIC plotting utility is used to audit the quality of transfers. Systems can be configured to automatically email users waveform captures as an attachment. This ensures that users are notified of events as they happen, without having to manually check for waveform captures.

Connectivity Features

  • Ethernet Connectivity: This protocol is used to connect the switch to a network.
  • Modbus/TCP: This protocol is used to communicate with BMS systems.
  • SNMP Connectivity: This protocol is used to manage the switch remotely.